Hamilton-sundstrand-company Fuel Metering Valves XVG Manuel d'utilisateur Page 28

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 27
Register
Number
XVG/eXVG Parameters
Name
Write
Access
Description Type
3099 IDM_TESTSTR[0]
3100 IDM_TESTSTR[1]
3101 IDM_TESTSTR[2]
3102 IDM_TESTSTR[3]
3103 IDM_TESTSTR[4]
3104 IDM_TESTSTR[5]
3105 IDM_TESTSTR[6]
3106 IDM_TESTSTR[7]
3107 IDM_TESTSTR[8]
3108 IDM_TESTSTR[9]
3109 IDM_TESTSTR[10]
3110 IDM_TESTSTR[11]
3111 IDM_TESTSTR[12]
3112 IDM_TESTSTR[13]
3113 IDM_TESTSTR[14]
3114 IDM_TESTSTR[15]
W0
Test string, used for Modbus write access password.
IDM_TESTSTR is an ASCII string array with
maximum of 16 elements. The string start at register
3099 and a Null (0) character is required to end the
string. Example: To enter PASSWORD, write:
80 to register 3099
65 to register 3100
83 to register 3101
83 to register 3102
87 to register 3103
79 to register 3104
82 to register 3105
68 to register 3106
0 to register 3107
ASCII
3115
IDM_AO0CHCFG
W2
Analog output channel 0 electrical configuration
selector. Can be used to automatically set output
configuration. Sets parameters when value assigned in
setup state. (Parameter is not stored in EEPROM.)
Returns configuration code when read is commanded.
0 = 4to20mA, 1 = 0to5V, 2 = 1to5V, 3 = 0to-5V.
When reading, an invalid setup returns “99”. An
invalid write returns SETUPERROR = 9001.
U16
3116
IDM_AO1CHCFG
W2
Analog output channel 1 electrical configuration
selector. Can be used to automatically set output
configuration. Sets parameters when value assigned in
setup state. (Parameter is not stored in EEPROM.)
Returns configuration code when read is commanded.
0 = 4to20mA, 1 = 0to5V, 2 = 1to5V, 3 = 0to-5V.
When reading, an invalid setup returns “99”. An
invalid write returns SETUPERROR = 9002.
U16
3117
IDM_AI0CHCFG
W2
Analog input channel 0 electrical configuration
selector. Can be used to automatically set input
configuration. Sets parameters when value assigned in
setup state. (Parameter is not stored in EEPROM.)
Returns configuration code when read is commanded.
0 = 4to20mA, 1 = 0to5V, 2 = 1to5V. When reading,
an invalid setup returns “99”. An invalid write returns
SETUPERROR = 9003.
U16
5000 5001 IDM_POSMANSTPT RO Not used, SW test parameter U32
5002 5003 IDM_CURMANSTPT RO Not used, SW test parameter U32
5004 5055 IDM_VALVEDMD RO Position Demand, counts 683-3413 U32
5006 5007 IDM_VALVESTATUS RO Position Status, counts 683-3413 U32
5008 5009 IDM_FVALVEDMD RO Fault Report Variable, not used U32
5010 5011 IDM_FVALVESTATUS RO Fault Report Variable, not used U32
5012 5013 IDM_FDATE RO Fault Report Variable, not used U32
28
Vue de la page 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 34 35 36

Commentaires sur ces manuels

Pas de commentaire