All XVG/eXVG parameters can be uploaded using Modbus Read Registers
function then convert the results into appropriate number representation for display
and monitoring. Model number and part number need to be converted into ASCII
character string. All registers are readable, choose whichever parameters are of
interest and read them.
10.2 Accessing Fault Records Procedure
The following parameters will be used to retrieve the XVG/eXVG fault records.
There are a maximum of 16 records available in the valve. The first eight are
permanent records, the other records are updated on a first-in first-out basis. When
there were 16 fault records in the valve, the oldest non-permanent record will be
deleted when a new fault record is created.
Register
Number
XVG/eXVG Parameter Name Description Type
Write
Access
3028 IDM_FRUNTMMINS Fault Log, Run Time Minutes of fault log U16 RO
3029 IDM_FRUNTMSECS Fault Log, Run Time Seconds of fault log U16 RO
3043 IDM_FRECORDNO Fault Log Record No, selects fault log record, 0-
16
U16 W0
3044 IDM_FFAULTCODE Fault Log, Fault Code of fault log record U16 RO
3045 IDM_FRECORDS Fault Log, Number of faults in fault log record U16 RO
3094 IDM_TESTCTRL Use to trigger EEPROM tasks (sets bits in
ETFLAGS). Fully functional using PECC
protocol. Using Modbus, only fault read task
allowed. See ETFLAGS for bits.
U16
W0
5026 IDM_FTOTALHRS Fault Log, Total Hours of fault log record U32 RO
5028 IDM_FRUNTMHRS Fault Log, Run Time Hours of fault log U32 RO
7050 IDM_FVOLTS3PT3 Fault Log, Volts3pt3 at time of fault Float RO
7052 IDM_FSOLTEMP Fault report variable, not used Float RO
7054 IDM_FINPUTPRES Fault Log, InputPres at time of fault Float RO
7056 IDM_FOUTPUTPRES Fault Log, OutputPres at time of fault Float RO
7058 IDM_FGASTEMP Fault Log, GasTemp at time of fault Float RO
7060 IDM_FFLOWRANGE Fault report variable, not used Float RO
7062 IDM_FMEASFLOW Fault Log, MeasFlow at time of fault Float RO
7064 IDM_FFAULTDATA Fault Log, Fault Data at time of fault Float RO
7066 IDM_FPOSININCHES Fault Log, PosInInches at time of fault Float RO
7068 IDM_FTEMPAMB Fault Log, TempAmb at time of fault Float RO
7070 IDM_FVOLTSPOS15 Fault Log, VoltsPos15 at time of fault Float RO
7072 IDM_FVOLTSNEG15 Fault Log, VoltsNeg15 at time of fault Float RO
Table 24: Fault Records Parameters